The Future of Monitoring

2000

Fully programmable, Monitor unattended or remote sites 24 hours a day. Data Log up to 32,000 records. Communicate by fax, phone, pager, e-mail, computer or even by Web Page!

Monitor up to eight analog or digital conditions of your choice (room temperature, outside temperature, humidity, tank levels, tank temperature, pressure, flow rates, flooding, HVAC controllers and more), plus power failure.

Select up to 32 destinations in any combination of phone, fax, numeric and alphanumeric pager, e-mail, and computer, to receive alarm messages or status reports. The 2000 is as versatile as you require.

With a single phone call you can receive a voice status report or data connection for more detailed information.

Line-seizure function to "grab" the phone line in an emergency situation.

Built-in data logging lets you log activity such as trends, usage and other factors -- up to 32,000 time-stamped records.

Program, view & monitor input activity in real time via an array of on-screen input gauges, graphs and bar monitors. Programming is easy point-and-click.

Analyze stored data (up to 32,000 time-stamped records of selected inputs, power and/or battery voltage), and even process incoming alarms. You choose how often data is sampled, and how often it's distributed.

Free Microsoft Windows™ compatible software. Compatible with Windows 3.1, Windows 95, 98, ME, NT and Windows 2000. Point-and-click programming. Real-time graphics. 3D charts and graphs for data logging.

Now create updating Web Pages! View monitored data as a page on your web site.

2000 Features

SENSAPHONE 2000 -- How did you manage without it?


SENSAPHONE 2000 SPECIFICATIONS :

DIALING PARAMETERS:
Programmable call list for each input
Alarm acknowledgment: touch tones, callback, or modem
Call progress monitoring: detect dialtone, busy signals, & ringback
Programmable time between calls: 30 seconds to 60 minutes

DESTINATIONS:
32 destinations: 36-digit telephone numbers, 64 character E-mail addresses

INPUTS:
1 AC Power and 8 Universal inputs: normally open/closed contact, 2.8K/10K thermistor,
4-20mA current loop, or 0-5V analog voltage
10 bit resolution

COMMUNICATION TYPES:
Voice, Fax, Modem, Internet E-mail, Numeric Pager, Alpha-Numeric Pager, Web Page posting.

SPEECH TECHNOLOGY:
User-recordable voice for 8 input alarm messages & one ID message

DATALOGGING:
Up to 32,000 samples (all samples include date and time)
1 second to 200 hour sampling rate
User-programmable channel selection: inputs 1-8, AC power, & NiCad battery backup

COMMUNICATION PORTS:
RS232 Programming Port: Used for local programming & set up
DB25 female DCE
38,400 bps

BUILT IN DATA MODEM:
Data throughput 14,400 bps
14,400 bps Fax
Protocols: V.32bis, V.32, V.22bis, V.22A/B, V.23, V.21, Bell 212A &103

LOCAL INDICATORS:
Inputs 1-8 Alarm Status LEDs
System On LED
Power Alarm LED
Phone LED
Battery OK LED

POWER REQUIREMENTS:
External transformer 120/220V AC 50/60Hz 10W
(UL listed power supply)
(6) C-cell Rechargeable NiCad batteries (not included)
10 hr battery backup

OPERATING TEMPERATURE RANGE:
0-50°C (32-122°F)

HUMIDITY:
0-90% RH, non-condensing

Size: 12.1"W x 7.2"H x 1.6"D

Shipping weight: 3 lbs.

 